Product Details:
Electrical Connection | Screw terminals up to max. 1.5mm2 |
Supply Voltage | 8-35V DC |
Response Time | 10-80 s |
Measuring Range | 0-60degC |
Sensitivity Error at Full Scale | +-.1degC |
Storage Temperature Range | -40-60degC |
Exact dew point monitoring is increasingly playing a
more important role in many industrial applications,
such as drying processes, air pressure pipelines, etc.
For these purposes the multifunctional EE35 Series
offers the ideal features.
The EE35 Series is based on a functional, user-friendly
housing concept and on the proven polymer humidity
sensors of the HC Series.
Typical Applications:
Product Details:
Supply Voltage | 21-28V DC |
Accuracy | 5ppm + 20% of reading |
Measuring Range | 20-200000 ppm |
Working Temperature Range | -40-70degC |
Selectable and Scaleable | 0 - 10V |
Response Time | 80 sec |
The exact monitoring of dew point temperature in compressed air systems, dryers for plastic and other industrial processes is becoming increasingly more important.
The EE375 is designed for measurement of low dew
points in OEM applications down to -60°C (-80°C). The core of the transmitter is the monolithic measurement cell type HMC01 developed by E+E Elektronik in thin-film technology.
An autocalibration procedure which is integrated in the
device and years of experience in low humidity adjustment make an accuracy of <2°C Td (±3.6°F Td) possible. The transmitter has one analogue output for dew point, frost point or ppm volume concentration.
Product Details:
Supply Voltage | 10-30V DC |
Accuracy | 5ppm + 9% of reading |
Response Time | 80 sec |
Measuring Range | 20-200000 ppm |
Storage Temperature Range | -40-60degC |
Sensor Protection | Stainless steel sintered filter |
EE371 series with a measuring range -80…60°C Td (-112…140°F Td) and EE372 series with a measuring range -40…60°C Td (-40…140°F) are the ideal solution for such applications.
The core of the transmitter is the monolithic measurement cell type HMC01, developed by E+E Elektronik in thin-film technology.
An autocalibration procedure which is integrated in the
device and years of experience in low humidity adjustment make an accuracy of <2°C Td (±3.6°F Td) possible.
The compact construction in a robust aluminium housing
and the numerous options allow easy mounting and many application possibilities.
Typical Applications:
Product Details:
Accuracy | 5 ppm + 9 % from measured value |
Analog Output | 4 - 20 mA (3-wire technology) |
Maximum Adjustable Scaling | -100-80degC Td (-148-176degF Td) |
Measurement Range | 20 -200000 ppm |
Resolution of Analog Output | 2 uA |
Response Time | Less than 15 sec |
The compact EE355 Dew Point Transmitter with a measuring range down to -60 °C Td is ideal for applications in compressed air systems, plastic dryers and industrial drying processes. An integrated auto-calibration procedure permits a measurement accuracy of
The measured values for dew point, frost point or ppm volume concentration are available on an analog 4-20 mA and a digital Modbus RTU output. Integration into the measurement task is simplified by the compact design and the exceptionally robust stainless steel housing.
With an optional Modbus to USB convertor and the free EEPCS configuration software the user can adjust the transmitter, set the Modbus parameters, and change the scaling of the analog output.